概述该低压隔离变压器用于工业低压网络的电气隔离及高次谐波电流的抑制。
技术规格(摘要)频率:50 Hz
K因子:20
输入电压:400 V
输出电压:400 V
一次绕组连接:三角形(Delta)
二次绕组连接:星形 + N
向量组:Dyn11
铁芯材料:M270 磁性钢
绕组材料:铜
静电屏蔽:置于一次与二次之间并接地
最高环境温度:40 °C
绝缘等级:H
绝缘水平:3
热等级:H
温升:125 K
最高海拔:1000 m
环境-气候-防火等级:E1 - C1 - F0
安装:室内
防护等级:IP00
参考标准:EN 60076 / IEC 61558(如适用)
产品型号DYN11 K20 CU IP00 7 | 7 kVA | 冲击电流:45 A | 空载损耗:150 W | 负载损耗:220 W | Vcc %:3.5
DYN11 K20 CU IP00 9 | 9 kVA | 冲击电流:45 A | 空载损耗:170 W | 负载损耗:270 W | Vcc %:3.5
DYN11 K20 CU IP00 10 | 10 kVA | 冲击电流:45 A | 空载损耗:180 W | 负载损耗:340 W | Vcc %:3.5
DYN11 K20 CU IP00 14 | 14 kVA | 冲击电流:42 A | 空载损耗:210 W | 负载损耗:370 W | Vcc %:3.5
DYN11 K20 CU IP00 18 | 18 kVA | 冲击电流:42 A | 空载损耗:240 W | 负载损耗:440 W | Vcc %:3.5
DYN11 K20 CU IP00 22 | 22 kVA | 冲击电流:35 A | 空载损耗:270 W | 负载损耗:510 W | Vcc %:3.5
DYN11 K20 CU IP00 28 | 28 kVA | 冲击电流:28 A | 空载损耗:340 W | 负载损耗:540 W | Vcc %:4
DYN11 K20 CU IP00 36 | 36 kVA | 冲击电流:26 A | 空载损耗:400 W | 负载损耗:610 W | Vcc %:4
DYN11 K20 CU IP00 45 | 45 kVA | 冲击电流:23 A | 空载损耗:460 W | 负载损耗:690 W | Vcc %:4
DYN11 K20 CU IP00 58 | 58 kVA | 冲击电流:21 A | 空载损耗:530 W | 负载损耗:800 W | Vcc %:4
DYN11 K20 CU IP00 63 | 63 kVA | 冲击电流:20 A | 空载损耗:570 W | 负载损耗:860 W | Vcc %:4
DYN11 K20 CU IP00 70 | 70 kVA | 冲击电流:19 A | 空载损耗:610 W | 负载损耗:920 W | Vcc %:4
DYN11 K20 CU IP00 80 | 80 kVA | 冲击电流:19 A | 空载损耗:650 W | 负载损耗:980 W | Vcc %:4
DYN11 K20 CU IP00 90 | 90 kVA | 冲击电流:18 A | 空载损耗:700 W | 负载损耗:1080 W | Vcc %:4
DYN11 K20 CU IP00 100 | 100 kVA | 冲击电流:17 A | 空载损耗:750 W | 负载损耗:1170 W | Vcc %:4
DYN11 K20 CU IP00 110 | 110 kVA | 冲击电流:16 A | 空载损耗:820 W | 负载损耗:1290 W | Vcc %:4
DYN11 K20 CU IP00 125 | 125 kVA | 冲击电流:15 A | 空载损耗:880 W | 负载损耗:1410 W | Vcc %:4
DYN11 K20 CU IP00 140 | 140 kVA | 冲击电流:15 A | 空载损耗:940 W | 负载损耗:1530 W | Vcc %:4
DYN11 K20 CU IP00 160 | 160 kVA | 冲击电流:14 A | 空载损耗:1010 W | 负载损耗:1680 W | Vcc %:4
DYN11 K20 CU IP00 180 | 180 kVA | 冲击电流:13 A | 空载损耗:1080 W | 负载损耗:1830 W | Vcc %:4
DYN11 K20 CU IP00 200 | 200 kVA | 冲击电流:13 A | 空载损耗:1160 W | 负载损耗:2010 W | Vcc %:4
DYN11 K20 CU IP00 225 | 225 kVA | 冲击电流:12 A | 空载损耗:1250 W | 负载损耗:2200 W | Vcc %:4
DYN11 K20 CU IP00 250 | 250 kVA | 冲击电流:12 A | 空载损耗:1340 W | 负载损耗:2400 W | Vcc %:4
DYN11 K20 CU IP00 280 | 280 kVA | 冲击电流:11 A | 空载损耗:1460 W | 负载损耗:2680 W | Vcc %:4
DYN11 K20 CU IP00 315 | 315 kVA | 冲击电流:11 A | 空载损耗:1570 W | 负载损耗:2960 W | Vcc %:4
DYN11 K20 CU IP00 350 | 350 kVA | 冲击電流:10 A | 空载损耗:1670 W | 负载损耗:3220 W | Vcc %:4
DYN11 K20 CU IP00 450 | 450 kVA | 冲击电流:9 A | 空载损耗:1930 W | 负载损耗:3890 W | Vcc %:4
DYN11 K20 CU IP00 580 | 580 kVA | 冲击电流:9 A | 空载损耗:2250 W | 负载损耗:4710 W | Vcc %:4
DYN11 K20 CU IP00 720 | 720 kVA | 冲击电流:8 A | 空载损耗:2580 W | 负载损耗:5580 W | Vcc %:4.5
技术参数- 频率:50 Hz
- K因子:20
- 输入电压:400 V
- 输出电压:400 V
- 一次连接:三角形
- 二次连接:星形 + N
- 向量组:Dyn11
- 铁芯:M270 磁性钢
- 绕组:铜
- 静电屏蔽:一次与二次之间接地
- 最高环境温度:40 °C
- 绝缘等级:H
- 绝缘水平:3
- 热等级:H
- 温升:125 K
- 最高海拔:1000 m
- 环境/气候/防火等级:E1 - C1 - F0
- 安装:室内
- 防护等级:IP00