Product IntroductionWith the rapid development of China’s electric power industry, preventive experiments on electrical appliances are important for ensuring the safe operation and maintenance of power systems. Insulation diagnosis is a key method for detecting insulation conditions or failures of electrical equipment. This series of instruments is specially designed for testing the electrical insulation resistance characteristics of large high-voltage transformers, electrical appliances, remote power cables or buried cables under high-interference conditions such as high-voltage substations and power plants.
Product ParametersRated testing voltage: 0.5kV, 1kV, 2kV, 2.5kV, 5kV, 10kV, 15kV, 20kV (8 voltage output gears in total)
Upper limit of measuring range: 100GΩ ~ 5TΩ
Lower limit of measuring range: 0.1MΩ
Output voltage error: ±5%
Short-circuit current: Approx. 5mA
Grade of accuracy: Grade 5.0
Basic error of second half measuring range: ±(5% · Rx + 1d)
Basic error of first half measuring range: ±(10% · Rx + 2d)
High voltage display error: ±(5% · Ux + 1d)
Temperature measuring error: ±0.5℃
Air humidity measuring error: ±2%RH
Power supply: 14.8V lithium battery
Service life of battery after one-time charging: 30 days, 10 times of DAR and 5 times of PI test per day
Insulation resistance: >500MΩ (between the test line and machine case)
Voltage resistance: AC10.0kV 50Hz 1min (between the test line and machine case)
Working temperature and humidity: 0℃ ~ +40℃, Storage temperature and humidity: -20℃ ~ +50℃, Boundary dimension: 270(L) x 240(W) x 165(H) (mm)
Weight: ≈4.5kg
Product Features- Microcomputer control with menu operation and large-screen LCD dot matrix display; intelligent instrument with stable performance.
- Strong anti-interference capability; applicable in environments with severe electromagnetic interference.
- Equipped with 8 voltage output gears: 0.5kV, 1kV, 2kV, 2.5kV, 5kV, 10kV, 15kV, 20kV.
- High voltage output can be regulated continuously.
- Automatic measurement of R15, R60, R600 and automatic calculation of DAR and PI.
- Strong load capacity; short-circuit current approx. 5mA.
- Measuring range 0 to 5TΩ with automatic range switching.
- Combination of simulation bar pointer and digital display shows data trend and accurate results.
- Testing time can be displayed at any time; buzzer reminder every 15 seconds.
- Automatic discharge of high voltage after measurement; discharge time ≤ 30 seconds.
- Automatic measurement of ambient temperature, air humidity and recording of date/time for each test.
- Can save 60 groups of measuring results; data retention up to 20 years.
- RS232 serial interface for communication with a computer.
- Printable measuring results.
- Automatic power-off after 5 minutes of operation (system beep prompt before shutdown).
- Comprehensive protection functions for high operational reliability.
Caractéristiques / Spécifications techniques- Modèle: UHV-825
- Plages de tension de test: 0.5kV / 1kV / 2kV / 2.5kV / 5kV / 10kV / 15kV / 20kV
- Plage de mesure: 0.1MΩ à 5TΩ
- Erreur de sortie de tension: ±5%
- Courant de court-circuit: ≈5mA
- Classe de précision: 5.0
- Erreur de température: ±0.5℃
- Erreur d'humidité: ±2%RH
- Alimentation: batterie lithium 14.8V
- Autonomie après charge: jusqu'à 30 jours selon usage décrit
- Isolement entre ligne de test et boîtier: >500MΩ
- Résistance diélectrique: AC10.0kV 50Hz 1min (entre la ligne de test et le boîtier)
- Température de travail: 0℃ ~ +40℃
- Humidité de travail:
- Dimensions (L x W x H): 270 x 240 x 165 mm
- Poids: ≈4.5 kg
- Mémoire: 60 groupes de résultats, conservation annoncée jusqu'à 20 ans
- Interface: RS232 pour communication PC